How to select a fire damper: an engineer's guide

Breaking down the key parameters for selecting fire dampers: type, activation temperature, fire resistance, actuator, certification.

How to select a fire damper: an engineer's guide

Fire damper is one of the key elements of a building's fire safety system. Human lives and property preservation depend on proper selection. This article examines the main parameters to consider when selecting.

  • 1. Valve Type • Normally Open (NO) — installed on standard ventilation systems, closes in case of fire. Activation temperature 70°C. • Normally Closed (NC) — installed on smoke extraction systems, opens in case of fire to remove smoke. Activation temperature 280°C (overheat protection).
  • 2. Fire resistance Main classes according to EN 1366-2: • EI 30 — 30 minutes • EI 60 — 60 minutes (most common for business centers and shopping malls) • EI 90 — 90 minutes (for high-rise buildings and underground structures) • E 600 — withstands 600°C for 60 minutes (for smoke extraction systems)
  • 3. Actuator • Manual — for budget solutions where automation is not required • Electromagnetic — triggers on fire alarm signal, power supply 24V • Electric reversing — for smoke exhaust systems, power supply 230V/24V • Spring return — fail-safe closing upon power loss
  • 4. Tightness (Leakage) Tightness classes according to EN 1751: • Class 1 — maximum tightness (leakage<10 м³/(ч·м²) при 500 Па) • Class 2 — средняя • Class 3 — стандартная

    For air conditioning systems, we recommend Class 1-2; for general ventilation, Class 3.

  • 5. Certification For EAEU countries (Kazakhstan, Belarus, Armenia, Kyrgyzstan, Russia), the following are mandatory: • EAC certificate TR CU 004/2011 (safety of machinery and equipment) • EAC certificate TR CU 020/2011 (electromagnetic compatibility) For Europe — CE declaration EN 1366-2, EN 1506.
  • 6. Dimensions Standard sizes — from 100×100 to 2000×2000 mm. For non-standard sizes, manufacturing per customer drawings is possible (lead time +5-7 days).

    Conclusion When selecting a fire damper, always consult with a design engineer. Incorrect selection may lead to system failure during a fire and fines from the fire inspection authority.